There are five current output modes: flow output, heat output, cold output, heat & cold output and flow direction output.
Flow output: current is output as instant flow percent, the percent means the flow percent.
Heat output: current is output as instant heat percent, the percent means the heat percent.
Cold output: current is output as instant cold percent, the percent means the cold percent.
Heat & cold status output: current is output as instant heat or cold status. When in heat status, current output is 20mA. When in cold status, current output is 4mA.
Flow direction output: current is output as the flow direction. When the direction is reverse, the current is 20mA. When in the positive direction, the current is 4mA.
Range setting of flow, heat and cold
Meter range setting is to set the flow upper limit, and the lower limit is set to "0" automatically.
The meter range setting decides the range of the meter, and also decides the meter percent display, meter current and correspondence between frequency output and flow, heat and cold.
Meter percent display value = (measured flow value / meter range) * 100%
Meter current output value = (measured flow value / meter range) * 20mA + 4mA
Meter frequency output value = (measured flow value / meter range) * frequency full range