Customization: | Available |
---|---|
After-sales Service: | No |
Warranty: | No |
Still deciding? Get samples of US$ 6.5/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Enter | |
input signal | Thermal resistance (RTD), thermocouple (TC) |
Cold junction compensation range | -20~60ºC |
Compensation accuracy | ±1 ºC |
Output | |
output signal | 4~20mA/hart |
Load Resistance | RL≤(Ue-12)/0.021 |
Upper and Lower limit overflow alarm output current |
IH=21mA,IL=3.8mA |
Power supply | |
Supply voltage | DC12~40V |
Other parameters | |
Temperature drift | 0.02%FS/ºC |
Response time | 1s reaches 90% of final value |
Working temperature | -40~80ºC |
Stored temperature | -40~100ºC |
Shock resistance | 4g/2~150Hz |
installation angle | Unlimited |
Installation area | b-type top box mounting |
Electromagnetic | Meet the requirements of gb / t18268 industrial equipment |
Model | Types | Measuring | Minimum | Measuring | Conversion | Note:
1.The above accuracy data is obtained by testing under the environment temperature of 20 ºC
± 2 ºC.
2.The output accuracy "%" is relative to the set range. 3.The cold junction compensation error needs to be added when measuring the
thermocouple. |
RTD |
Pt100 | -200.0~850.0ºC | 20ºC | ≤100ºC | 0.2% | |
>100ºC | 0.1% | |||||
Cu50 | -50.0~150.0ºC | 20ºC | ≤100ºC | 0.2% | ||
>100ºC | 0.1% | |||||
TC |
B | 400~1800ºC | 500ºC | ≤300ºC | 0.2% | |
>300ºC | 0.1% | |||||
E | -100~1000ºC | 50ºC | ≤300ºC | 0.2% | ||
>300ºC | 0.1% | |||||
J | -100~1200ºC | 50ºC | ≤300ºC | 0.2% | ||
>300ºC | 0.1% | |||||
K | -180~1372ºC | 50ºC | ≤300ºC | 0.2% | ||
>300ºC | 0.1% | |||||
N | -180~1300ºC | 50ºC | ≤500ºC | 0.2% | ||
>500ºC | 0.1% | |||||
R | -50~1768ºC | 500ºC | ≤500ºC | 0.2% | ||
>500ºC | 0.1% | |||||
S | -50~1768ºC | 500ºC | ≤500ºC | 0.2% | ||
>500ºC | 0.1% | |||||
T | -200~400ºC | 50ºC | ≤500ºC | 0.2% | ||
>500ºC | 0.1% |